7 Day, 15 Amp

This series provides photo control initiated / time switch terminated control. These time switches provide a different “ON/OFF” program each day of the week and a spring wound carryover. These time switches are recommended for applications where you need to turn a load “ON” at dusk and “OFF” at a preset time. The spring wound carryover provides a carryover of 16 hours minimum to maintain accurate load control even during power failure. When power resumes, the carryover automatically rewinds itself. Only 1 hour is required to rewind the carryover for each 2 hours of outage. The three models provide control of 1, 2 or 3 circuits. A light level adjustment is provided on the photo control. All models have single pole double throw switches and manual circuit by-pass switches.

Unit is designed to control the contactor control circuit only. It is not recommended for direct switching of tungsten, mercury vapor or similar loads.

Specifications

  • Case – Steel in gray finish 12-1/2" (31.7 cm) high, 8-1/4" (21.0 cm) wide, 4" (10.2 cm) deep. Indoor type with toggle action drawbolt and locking feature. Four mounting holes on back. Separate grounding terminal.
  • Knockouts – Combination 1/2"-3/4" nominal knockouts, two on back one on each side and two on bottom. Also one 1" nominal on bottom center.
  • Optional Enclosures – None available
  • Contact Rating – 15 Amp, 1/2 HP, 125/250 VAC; 420 VA pilot duty; 150 Watts Tungsten, 125 VAC (May also be used with 24 volt systems if wired in accordance with National Electrical Code Regulations.)
Model Circuit A Circuit B Circuit C Clock Motor Volts 60 Hz
T51211BCSunset, Photo Control ON; Preset Time Switch OFFSunset, Photo Control ON; Sunrise, Photo Control OFF-120
T51311BCSunset, Photo Control ON; Preset Time Switch OFFSunset, Photo Control ON; Sunrise, Photo Control OFFPreset Time Switch ON; Preset Time Switch OFF120