24 Hour Dial
Designed for industrial, commercial and residential applications. Highest HP ratings in the industry for loads up to 40 amps, providing direct 24 hr. control of most loads. Provides 1 to 12 “ON/OFF” operations each day with minimum ON/OFF times of 1 hour. All models equipped with one “ON” and one “OFF” tripper.
Specifications
- Case – Drawn steel 7-3/4" (19.7 cm) H, 5" (12.7 cm) W, 3" (7.6 cm) D in gray finish. Spring hasp, with hole for lock, holds permanently attached, side hinged door closed. Three mounting holes on back plus handy box mounting holes.
- Knockouts – Combination 1/2"–3/4" nominal knockouts, one on back and each side of case and two on bottom.
- Optional Enclosures – See Time Switch Cases page for optional enclosures.
- Special Voltages and Cycles – See Time Switch Motors page for available motors.
- Switch Rating – Each Pole; 40 Amp Resistive, 120-480 VAC; 40 Amp Tungsten, inductive or 1000 VA pilot duty, 120-277 VAC; 2 HP (24 FLA) 120 VAC; 5 HP (28 FLA) 240 VAC single phase; 7-1/2 HP (28 FLA) 208 VAC three phase; 10 HP (28 FLA) 240 VAC three phase.
| Model |
See-Thru Cover |
Plastic Case |
NEMA 3R Case |
Switch |
Clock Motor Volts 60 Hz |
Amps (per pole) |
HP Rating |
|---|
| T101 | T101PCD82 | T101P | T101R | SPST | 125 | 40 | 2 |
|
| T102 | - | T102P | T102R | SPST | 208-277 | 40 | 5 |
|
| T103 | T103PCD82 | T103P | T103R | DPST | 125 | 40 | 2 |
|
| T104 | T104PCD82 | T104P | T104R | DPST | 208-277 | 40 | 5 |
|
| T105 | - | - | - | 1NO / 1NC | 125 | 40 | 2 |
|
| T106R | - | - | T106R | 1NO / 1NC | 208-277 | 40 | 5 |
|
|