24 Hour Electronic (8 Set Points)

These time switches provide the same dependable and uncomplicated performance as the T101 mechanical time switch...plus to-the-minute programming for accurate load control and reduced energy costs. Up to 8 set points or events (4 ON/4 OFF) can be preset to automatically repeat on a daily basis. The program can be overridden at any time by placing the selector switch in the Manual position. Two industrial grade “AA” Alkaline batteries provide 3 years minimum program and timing protection.

Specifications

  • Case – NEMA 1 – Drawn steel 7-3/4" (19.7 cm) High, 5" (12.7 cm) Wide, 3" (7.6 cm) Deep in gray finish Note: The electronic mechanism snaps into the standard Intermatic time switch case, replacing mechanical mechanisms, if desired.
  • Knockouts – Combination 1/2"-3/4" nominal knockouts, one on back and each side of case and two on bottom
  • Optional Enclosures – See Time Switch Cases for optional enclosures
  • Special Voltages and Cycles – ALL models 50 or 60 Hz
  • Switch Rating – Except model ET100C. 30 Amp Inductive/Resistive, 24 / 120 / 240 / 277 VAC 60 Hz; 20 Amp Resistive, 28 VDC; 1 HP 120 VAC 60 Hz; 2 HP 240 VAC 60 Hz; 5 Amp Tungsten, 120 / 240 / VAC 60 Hz; 20 Amp ballast,120-277 VAC 60 Hz. ET100C same ratings for 120 Volt loads only. Models ET105C normally closed contact ratings: 10A Resistive/General purpose, 12 - 277VAC; 10A Resistive/General purpose, 28VDC; 3A Ballast, 120 - 277VAC; 1/4 HP, 120 VAC; 1/2 HP, 240 VAC; 30 LRA; 12 FLA; 275 VA pilot duty, 120 - 240 VAC
  • Carry-over – Field replaceable “AA” batteries maintain program and accurate time keeping for 3 years minimum. Up front replacement does not require removal of mechanism or field wiring.
  • Wiring Terminals – #18 to #10 AWG wire
  • Minimum ON/OFF Times – 1 minute
  • Maximum ON/OFF Times – 23 hours 59 minutes
Model Circuits Switch Clock Voltage Amp Rating HP Rating Enclosure
ET100C1SPST120301 HPNEMA1
ET101C1SPST120301 HP / 2 HPNEMA1
ET102C1SPST120 / 208 / 240 / 277301 HP / 2 HPNEMA1
ET103C1DPST120301 HP / 2 HPNEMA1
ET104C1DPST120 / 208 / 240 / 277301 HP / 2 HPNEMA1
ET105C1SPDT12010 / 301 HP / 2 HPNEMA1
    • After properly programming my ET100 Series Timer it will not activate my power load.

      Check to make sure that you have placed line power or voltage on the designated line terminals. If you are powering your load with the same line voltage you are powering the timer with, jumper this voltage over from terminal number 2 to each line terminal.